2026-09-28
The valve is not opening when the coil is energized..
If valve is not opening when the coild energized;
Power supply might be low, wrong or none. It should be sending to correct voltage and frequency to the coil.
Solution
Check your power supply, coil and connections.
Wrong position valve might be chosen. Normally Closed Solenoid Valve goes open position when it is energized and Normally Open Solenoid Valve is closed when it is energized.
Solution
Check the position of the valve by its order code
Pilot Orifice might be clogged.
Solution
Take the core tube(stem) apart and clean the all components in it and orifice as well.
Diaphragm, seal or piston might be damaged.
Solution
Replace with the new sealing part
The plunger might be stucked in the tube or adherent on the orifice due to dirt or corrosion
Solution
Disassemble the core tube and clean the plunger and inner surface of the core tube
Inlet pressure might be higher than the maximum operating pressure
Solution
Check if the line pressure is comply with the product's informed pressure on catalogue
The differeantial pressurue (P1-P2) might not be enough to operates the valve
Solution
Check your line pressure. Indirect (pilot operated) solenoid valves need an appropriate differantial pressure to work and never be able to work in closed loop nor gravity feed systems.
Coil might be burnt out
Solution
Replace with the original one
